Annual Testing of Backflow Prevention Assemblies

Backflow Prevention Devices

Forms

FAQ

Backflow Prevention Devices
Air Gap drawing An air gap is a vertical, physical separation between the end of a water supply outlet and the flood-level rim of a receiving vessel. This separation must be at least twice the diameter of the water supply outlet and never less than 1 inch.

An air gap is effective against backpressure backflow and back-siphonage and may be used to isolate health or non-health hazards.
RPBA drawing A Reduced-pressure Principle Backflow Assembly (RPBA) includes two independently acting, spring-loaded check valves with a hydraulically operating, mechanically independent, spring-loaded pressure differential relief valve in between. Testing is required for this type of BPA. An RPBA is effective against backpressure backflow and back-siphonage and may be used to isolate health or non-health hazards.
PVB drawing A Pressure Vacuum Breaker (PVB) consists of an independently acting, spring-loaded check valve and an independently acting, spring-loaded, air inlet valve. This assembly requires testing. A PVB may be used to isolate health or non-health hazards but is effective against back-siphonage only.
DCVA drawing A Double Check Valve Assembly (DCVA) consists of two independently acting, spring-loaded check valves. This type of assembly requires testing. A DCVA is effective against backpressure backflow and back-siphonage but should be used only to isolate non-health hazards.